Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. EHS observed equalizer covers expired 3-2-25. EHS is required to deny permit for pool until covers are replaced and proper documentation sent to meckpools@mecknc.gov for approval prior to next re-inspection. EHS advised to keep spa closed until pool is permitted. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Horizontals shall not be located less than 45" in height. Horizontals on fencing distanced less than 45”. EHS observed potential foothold with brick walling around building that wraps between building and fence. The height of the brick wall is 33” from ground level, 4” offset from wall. Fence was built pre-2010.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". EHS observed opening between vertical bars greater than 4” due to bent bars. CDI - Operator was able to bend bars back to original position eliminating the distance to no greater than 4”. |