Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2517(a)1 Diving equipment shall be installed per manufacturer's instructions. Observed missing end caps on ladder close to the slides. Repair |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed the ring buoy rope more than 50’. CDI - CPO corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed doors to the pool from the clubhouse not self latching. CDI - CPO repaired door and is now self closing and self latching.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed all windows leading into the pool could open greater than 4”. CDI - CPO added screws to prevent the window from exceeding an opening of 4” |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. When EHS called the emergency phone the phone did not ring back. CDI - CPO changed the phone and is now ringing back to the pool when called. |