16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching. Observed entrance gate not self-closing and self latching.
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. Original gate latches have been changed to key fob latch from subcontractors per assistant general manager. Observed new crossbar mechanism located under 54” on interior of gate. However, space between vertices measuring greater than 1/2 in. Within 18” of latch mechanism. Provide no greater than 1/2 “ x 1/2” within 18” of latch mechanism in all directions. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed no pool telephone number posted. Phone number verified with 911 was 980-378-1562 and corrected on site. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap provided. |