NameRESIDENCE INN BY MARRIOTT
Address16830 KENTON DR
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 4/29/2016
Final Score @ Grade
24
General Comments5) Records not yet being kept. Check daily Cl, pH, temperature and main drains. Check at least weekly TA and CYA.Permit will be available onliine at Meckpools.charmeck.org within 1-3 business days.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH 7.0. Maintain between 7.2 and 7.8. Corrected to 7.2.
6 6 Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ No No No PDSC form states 2 equalizer lines. Pool has 3 equalizer lines. Provide updated Pool Drain Safety Form. Corrected form submitted and approved.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No One ladder missing non-slip tread. Provide non-slip tread for ladder.Both ladders missing endcaps. Provide endcaps.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No One of two ring buoys damaged. Remove damaged ring buoy or replace with USCG approved ring buoy.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan in chemical storage room not functioning. Provide cross or forced air ventilation for chemical storage room.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms > 110F. Maintain 110F or less.