Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.- Observed 4 missing equalizer covers out of 12 totals. Need replacement. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs.- Observed two missing weirs out of twelves total. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.- Observed 2 missing return line covers. Need replacement.
.2537(10) Diving equipment and pool slides including stairs and railings shall be kept in good working order.- Observed one disrepair stair. In the process of fixing. Keep in good working order. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed back gate “Exit only” sign posted. It is magnetic gate, it will come close to magnet when swing open, and depending on direction and way, it may latch completely. And this case it doesn’t latch more than half of the time. It didn’t close completely as it should, left access to the pool. This gate shall be repaired and ensure it works properly in timely manner. |