| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No total alkalinity or cyanuric acid checks. Check daily Cl, pH, main drains and at least weekly total alkalinity and cyanuric acid. - Intent to suspend item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form does not match what is installed. Observed 8HP EQ covers in place. - New approved PDSC form filled out by operator. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty. Vacuum regularly. Corrected.
Pool needs repained/replastered, bare concrete. Some chipping on pool walls. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers missing weirs. Install functional weirs. Corrected by operator.
Two skimmers with plugs in return. Provide functional skimmers. Plugs drilled out by operator. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladders loose, one missing endcaps. Maintain secure and in good condition. Corrected by operator.
Handrail loose. Escutcheons bent. Maintain secure and in good condition. Corrected by operator. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Missing inlet fittings. One return line plugged. Provide functional returns and inlet fittings. Corrected by operator. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One body hook damaged, one ring buoy missing 50 foot throw rope. Items removed from pool deck. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Openings > 4" through fence, two fence sections not secured. Maintain secure fence > 48" w/ no gaps > 4" through fence. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Hole in deck where new pad meets old pad. Maintain deck with no openings or offsets > 1/2". |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Provide signage in at least 1 inch lettering stating "CHILDREN SHOULD NOT USE THE SWIMMING POOL WITHOUT ADULT SUPERVISION" and "ADULTS SHOULD NOT SWIM ALONE" Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Repair or replace. Corrected by operator.
Pressure guage on center filter not functioning. Provide functional pressure guage. Corrected by operator.
Provide sight glass for pool filters. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Store in chemical storage room.
General storage in chemical storage room. Store only chemicals in chemical storage room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Provide air gap for backwash. |