Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
GPM above required 80GPM setting. CPO corrected to 80GPM setting per approved PDSC. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions.
Ladders without end caps. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy rope extending past approved length. CPO cut and knotted rope to proper length. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
Fence with clearance greater than 4” in areas around fence and near gate. CPO to move rocks to close gap under area. |