Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form lists Pentair Challenger CHII-NI-2F 2 HP, observed pump plackard on pump listed as Pentair Challenger CHII-NI-1/2F 1/2 HP. Need to complete a plan review application if pump has been changed or otherwise provide proof of installed pump. Sent application to PO by email. Have this completed in 3 days or pool permit will be suspended. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed fencing with foot holds 27" from ground with 6" gaps at fence from pool house. Maintain no more than 4" gaps in pool fence. Observed one area at bottom of pool fence with bottom clearance of 6". Maintain no more than 4" gap from bottom of fence. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room ceiling exhaust vent does not appear to be operating, and there is only one source of natural ventilation. Have exhaust fan repaired/ replaced or provide natural cross ventilation. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water observed above 110 in restrooms, needs to be 110 max. Mirrors not shatter proof in restrooms. Baseboard trim falling off wall needs refastening in men's restroom. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device observed on a few hose bibs connected to pool house. |