Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Observed Cl at 0ppm. Chlorinator valve had malfunctioned. Valve repaired during inspection and Cl was at 1.0ppm before inspection ended. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed some water on the pump room floor. Appears there may be a small leak in the PVC piping.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. None available. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(j) Provide soap and soap dispenser, no glass, at each sink. No soap was available.
.2626(m) Keep restrooms and fixtures clean and in good repair. Restrooms are in need of cleaning. |