Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form for pump model and Main drain covers do not match observed models in field. Pump listed at Sta-Rite P4E6H and Main drains listed as Wav12WRxxx, Observed pump Sta-Rite P4E6G and Main drains Aquastar P12xxx. Have form re-submitted for approval. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
1 of 3 weirs missing, need to install missing weir. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope observed at 48 ft, needs to be 42 ft. PO corrected rope length to 42 ft. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone observed not dialing out. Permit suspended until phone repaired. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Exhaust fans observed wired to wall switch, needs to be directly wired to run continuous. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Need backflow prevention device on hose bib next to restrooms.
GENERAL COMMENT: POOL SUSPENDED FOR ITEMS 6 AND 22. Have items corrected and call 704-336-5100 for re-inspection. |