Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8.
PH below 7.2 at start of inspection. Corrected to 7.3 during inspection. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Per permit restrictions, flow required at 140gpm. CPO had unit turned up while adjusting PH. After PH adjustment was complete unit was turned down and 140gpm was achieved. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions.
Ladder on backside of pool loose. Tightened during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Rope exceeded 45’ per permit restriction. Cut and knotted during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gaps between horizontal and ground at 6”
Gaps between verticals greater than 4” near brick columns.
Pool built prior to 2010 rule. |