| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
1
|
6
|
Water quality: water clear enough to clearly see bottom of pool and pool drain |
No |
No
|
No |
Pool cloudy. Drains not visible. Could not verify VGB. Ensure PDSC form matches what is in the field. Drains shall be clearly visible. Permit item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Maintain at 7.2 to 7.8. Permit item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Overflow not flush to pool wall. Part of renovation. Appears has settled and "popped out". Not sealed around it. Repair overflow so flush to wall. Permit item. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
New deck tile installed. Multiple depth markers not slip resistant. Deck tile shall be slip resistant with 6x6 inch tile. Permit item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
New decking installed. Ladder rungs 7" to 9" from wall. Ladder rungs shall be 3" to 6" from wall to rung. Permit Item.
New deck installed - pool steps >20 ft. wide. Step handrails >10 ft. apart. Handrails shall be 10 ft. apart or less.
Permit items above.
For all above items, electrical permit is required. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
New barrier installed in front of old barrier in previous year. New barrier has new gates and latching mechanisms.
Magnet lock installed on front of gate with horizontal. Horizontals less than 45" apart. Eliminate horizontal. Permit item.
>1/2" between post and gate. Maintain 1/2" or less. Permit item.
Push button on left side entry accessible. Maintain no openings >1/2" within 18" of locking mechanism. Permit Item.
Other items noted on old barrier. <45" between horizontals and openings greater than 1.75". Horizontals shall be 45" apart or greater with no openings >1.75". |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Fill line on deck located >6" from handrail. Fill line moved during deck repair. Fill line shall be within 6" of handrail. Fill line can be plumbed in pump room as direct fill if facility chooses. Permit item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Pool pH at 6.8. Feeder reading 7.4. Calibrate feeder. Permit item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Liquid chemicals not stored in chemical storage room. Store chemicals in the approved chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >113 F. Maintain at 110 F or below.
Toilet in men's restroom soiled. Keep fixtures clean. |