15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed rope length greater than 50ft. -CDI- CPO corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Ground level doors were not self-closing/self-latching or with audible alarm. -CDI- CPO corrected by turning alarm on. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed > 6ft clearance around pool deck. -CDI- CPO corrected. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Signage improperly worded. -CDI- CPO provided proper signage.
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Not mentioned on signage. -CDI- CPO provided proper signage. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed water on pump room floor. Per CPO, pump was leaking but repairs had been made, however, water had not fully dried. |