Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed two (2) of the eight total skimmers with missing weir doors. Replace and maintain skimmer weirs as required. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. Observed one (1) no diving marker heavily cracked and illegible. Distance between the adjacent no diving markers as the crow flies was less than 25’ (23 feet and 2 inches.) Replace damaged no diving markers as needed. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed one (1) partially unattached post in fencing, creating opening of approximately 4.9 inches. Pool was constructed pre-2010 and natural topography (plants, hills) prevents entry from outside of pool deck. Repair fencing as required.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed 2 ground level club house door leading to entrance of pool deck not self latching and with no audible alarms. CDI by adding audible alarms to doors. |