Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Checklist in log book did not include main drain checks. CDI: main drain check slot written in during inspection. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers and skimmer baskets in need of cleaning. CDI: cleaned during inspection.
.2518(k) Replace missing weirs. Observed 5 weirs missing. CDI: all weirs replaced during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. Observed one pole missing body hook due to it being damaged. CDI: pole with body hook was replaced. Observed the other pole with body hook missing the screws. CDI: screws replaced during inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed one out of the two ropes > 50ft. CDI: rope was corrected to 50ft during inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Observed cap/cover missing on vacuum line on pool wall. Vacuum line was turned off in pump room. CDI: cap was provided for vacuum line during inspection. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed no back flow preventer on deck hosebib used to fill pool. |