Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One equalizer line cover with large gap between cover and adapter plate. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. - Pre-permit item.
One equalizer line plugged in the wall, but had spring loaded pop-up cover in the skimmer. Will need to be abandoned per state guidelines per PDSC form. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Pre-permit item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir not installed. .2518(k) Provide functional weirs. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
More than 25 feet between some depth markers on pool wall. .2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. - Pre-permit item. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One eyeball fitting missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Corrected.
Fitting missing for auto-fill. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Pre-permit item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy with 32 foot throw rope. .2530(a) US Coast Guard approved ring buoy with 50 foot throw rope at least 1/4 inch in diameter. - Pre-permit item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Magnetic latch at main gate creates a foothold. .2528(b) Horizontals shall not be located less than 45" in height. - Pre-permit item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Water from shower leaks in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Shower not functioning. .2526(h) Shower(s) shall be provided. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Lights not working in women’s restroom. .2526(m) Keep restrooms and fixtures clean and in good repair. |