3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.9. Corrected to 7.2 during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Horizontals on service gate and fence less than 45", at time of inspection 37". Entry gate had horizontals less than 45", over 30", but additional mesh around fob entry and over horizontal. Pool built '01. .2528(b) Horizontals shall not be located less than 45" in height. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. No basket on site. Provided during inspection. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on hose bibb outside chemical room. Provide backflow preventer. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
.2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. Did not observe a hose bibb for the restrooms.
.2526(c) Floor drains shall be provided in restrooms. No floor drains in restrooms. |