3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. Corrected to 7.2. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed slight debris on pool floor. Vacuum as needed. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy in bad repair. CDI - Ring Buoy replaced by CPO. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed “WARNING” in 4” lettering, but not the no life guard part. CDI - Sign was replaced with 4” lettering on the entire phrase. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Observed automatic chlorine feeder continue running when pump is turned off.
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation. Observed automatic acid feeder continue running when pump is turned off.
PIC installed pressure switch during inspection. Feeders were automatically turning off by end of inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed continuous ventilation fan not in operation in chemical room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed hole in dry wall underneath men’s urinal. Repair. |