3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. PO corrected pH to 7.2, be sure proper pH is maintained. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope required to be 45 ft. observed at 40 ft. PO replaced rope with 45 ft rope. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Hose bib in men's restroom has no backflow prevention device. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Backwash pipe is directly piped, has no air gap.
GENERAL COMMENT: Depth a couple 4ft dept markers on pool wall are fading, need to be replaced by next season. All permit items corrected. Permit issued. |