| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public.
- Observed a ”LESLIES Chemical Floater” device is floating in the pool. Chlorination must occur through chlorinator at all times. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8.
- Observed pH measured at 6.8. pH levels shall be maintained between 7.2 and 7.8 at anytime. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
- Observed expired chemical test kit. Obtain a new test kit. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
- Observed PDSC form has Pentair Challenger pump, the actual pump inside the pump room is Hayward (Model# SP2610X15XE, Serial# 21122409003254018, THP= 1.65, WEF= 8.2) not matching.
NOTE: New PDSC form is to be submitted to the department and approved before issuing permit. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521(a) Recessed steps or ladders shall be provided at the deep portion of the pool.
- Observed missing ladder at the deep end of the pool. Also leaving holes on pool deck, made it tripping hazard. Replace the ladder.
.2521(b) Provide at least one handrail on steps.
- Observed missing handrail on steps down the pool leaving holes on pool floor and deck. Replace the handrail back. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
- Observed rope length is too long. CPO cut the rope and keep the required length at the time of inspection. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
- Observed holes on pool deck from missing ladder and handrail at each end of the pool. Replace the ladder and handrail back in place to keep original deck profile. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.- Observed missing phone number on the emergency pool signage. Item fixed at the time of inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational.
- Observed flow meter is not working properly. The red bubble got stuck at the top. Repair needed. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(c) Valves and controls shall be accessible to the pool operator at all times.
- Observed old appliances and stuff stored inside the pump room leaving minimal space to the pump and equipment. Maintain 3 ft. clear walking space in pump room. |