5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. No records available - no record book available on site.
.2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. CPO is based out of Greensboro and currently maintains pool 4 days per week. Pool must be maintained daily by a certified CPO and records must be maintained and available for review for every day the pool is open. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Algae buildup on bottom of pool floor. Operator cleaning during visit. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. No diving markers on pool walls not international 6 x 6 in red/black. Replace with correct tiles. Permit item |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 - Stairs leading into pool in poor repair with 2” open hole on bottom step where ladder removed/replaced. Hole must be repaired prior to permitting. Permit item |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope at 30”. Need to correct to 23’
Permit item.
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. Body hook not attached to pole. Operator corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Gate near office are not self closing and latching shut. Permit item
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Ground level windows in residential apartments not limited to opening no more than 4”. Correct. Permit Item |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Incorrect call back number for Kings III emergency system phone posted. Operator corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
.2534(6) Provide sufficient lighting in chemical storage room.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed standing water on pump room floor. All pool chemicals stored on floor in water on pump room floor and not inside attached chemical storage room. Ventilation not working in pump room or in chemcial storage room. Light not working in chemical storage room. |