6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
** Flow restriction: Pump must remain at a 95GPM (+/-5%) to meet flow rate **
Observed pump at 65GPM via flow meter. CDI - Pump was turned up - flow rate reading and retaining at 95GPM. Operator programmed VSP to remain required RPM to achieve required GPM for turnover. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. EHS observed deck furniture at a distance less than 6’ around pool deck. CDI - Operator pulled furniture out away from pool, creating a clear walking space of 6’. |