6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c)(1) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Documentation of the maximum possible flow rate for each pump suction system.
** Flow restriction: Pump must remain at a 95GPM (+/-5%) to meet flow rate **
Observed pump at 70GPM via flow meter. CDI - Pump was turned up - flow rate reading and retaining at 95GPM. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed slight debris present in pool. Clean as needed. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope at 60ft. Pool requirement is 30 ft rope. CDI - ROP cut to 30ft. |