Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
PDSC form was submitted and main drains covers were not replaced. All equalizer covers were replaced and installed properly annoying patch to PDSC information.
Main drains are expired.
PDSC form shows 12MFxxx
Covers observed Do not match the PDSC form.
Q-Status. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Observed 2 cracked skimmers on left corner of the pool (Casing).
In need of repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed safety ropes at 47 ft when required to be 50 ft.
CDI - Ropes lengthened to be 50 ft. |