| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No main drain checks. Record main drain checks daily. No cyanuric acid and total alkalinity checks recorded. Operator stated taking weekly. Record weekly. Intent to Suspend issued for record keeping. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algae around ladder rungs and equalizer lines. Continue to monitor. Treat as needed. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Missing deck depth marker above 3 ft. at main step entry into pool. Located on wall. Provide 3 ft. depth marker. Intent to Suspend issued.
>25 ft. between No Diving markers from right side of main entry step to next no diving on left side. Also for right side step entry. 25 ft. as the crow flies. Provide Deck NO Diving markers at 25 ft apart or less prior to 2024 operating season. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
End caps missing off ladders. Provide end caps. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Both ring buoy ropes too long. Cut to 50 ft. during the inspection. Grab rope on one ring buoy degrading. Replaced ring buoy during the inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
>1/2" meshing on gates. Openings shall not exceed 1/2". Repair prior to 2024 operating permit.
Pool fence less than 48" in height in some areas due to landscape and <45" between horizontals. Pillar tie into fence where fence not 48" in height. Pool built pre-2010. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool >1600 sq. ft. Some deck chairs too close to pool edge. 2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft).
Some deck damage where deck is popping. No offsets >1/2". May require repair in the future. Continue to monitor. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Small leak at multiport of right filter. Repair leak.
Pressure gauge not working on left filter. Repair. Intent to Suspend issued.
No spare pump basket for pump. Provide spare pump basket. Intent to Suspend issued. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention device on hose bib in pump room. Hose bib prior to check valve. Provide backflow prevention device. |