Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder > 6” from pool wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall to ladder rung.
Handrail not secure, easy to pull out of the pool deck. .2521 Install handrails per manufacturer instructions.- Will need to repair prior to 2027 permit being issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to office not self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items stored beside pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Bags of dry chemicals on the floor in the pump room. .2534(4) Provide provisions for dry storage in waterproof containers or above the floor on shelves, pallets or dollies. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
New piping not labeled. .2518(d) Piping and valves shall be labeled with color codes with a legend or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No soap in restrooms. .2526(j) Provide soap and soap dispenser, no glass, at each sink.
No toilet paper on toilet paper holders in most of the stalls. .2526(l) Provide toilet paper and dispensers in restrooms.
3 lights burned out in men’s restroom. .2526(m) Keep restrooms and fixtures clean and in good repair. |