6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC does not match what is installed. Observed 8 HP covers, form states 6HPA covers are installed. Pump is actually Pentair XFE-12 3 HP pump .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - PDSC form corrected and approved. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from fitness center tied to a motion sensor, push to exit button disabled. .2528(a) Ground level doors shall be self-closing and either self-latching or child protected by audible alarm. - Corrected. Sensor disabled and door now works on push to exit button. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some deck chairs too close to pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Most of the pump room floor is wet. .2533(d) Pump room floor shall be kept dry and free of standing water. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Both sets of restrooms locked. .2526(a) Provide at least one sink and toilet for residents and guests if furthest unit is more than 300 feet from the pool at hotels, motels, condominiums and apartments. - Restrooms temporarily locked while work is being done. |