Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form lists Aquastar 8HPxxx, observed 6HPxxx, have form corrected and re-submitted. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One skimmer box has been cemented to where an avg size weir cannot fit, no weir observed. PO will replace with custom fit weir. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One wall return line missing its eye lid cover, have replaced. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemical room ceiling exhaust fan wired to wall switch, needs to be directly wired to provide continuous ventilation
GENERAL COMMENT: Have items #6, 8, and 12 repaired before permit can be issued. |