9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(c) Depth markers shall include the word "feet" or symbol "ft". Observed most depth markers on pool deck missing FT symbol. Operator stenciled during inspection. Recommend replacing depth marker tiles that are missing the FT symbol. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope greater than 50’. Corrected to 41’ during inspeciton. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Under fencing around pool >4”. Some gaps under fence greater than 4”
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed two electrical junction boxes creating a foothold at <48” from bottom of fencing.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Gap between fence and and pump room greater than 4”
Pool built 1998. No permit action. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept in good repair. Observed cracking and degradation in concrete decking around pool perimeter with offsets approaching 1/2”. Decking will need to be repaired prior to 2025 operating season. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(b) Provide sufficient lighting in pump room. Lighting not operational in pump room.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Bags of dry chemicals stored on floor in chemical storage room,
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Vent fan not operational in pump room . |