| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Maintain pH at 7.2 to 7.8. Permit denial. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
CPO onsite could not provide card. Provide CPO certification for return inspection. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Equalizers installed not what is listed on the PDSC form. Form shows A10RCFRxxx covers which are sumpless. Installed Aquastar 10MFxxx. Current equalizers are not installed per mfg. instructions. Replace cover with a sumpless cover. PDSC form shall be submitted and approved with either new covers or new install date. Permit denial. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some minor chipping of paint on the pool floor. Does not present hazard at time of inspection. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir missing from skimmer closest to building. Replace weir. Permit denial. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
No Diving markers on pool deck not slip resistant. One 5 ft. depth marker on deck not slip resistant. Depth markers and no diving markers shall be slip resistant. Ensure, if provided on tile, shall be 6x6 tile. Permit denial. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Autofill missing fitting. Overflow grate damaged. Replace fittings. Keep in good repair. Permit denial. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Front gate not 48" in height on right side of gate. Gate shall be 48" in height. Permit denial.
Front gate with horizontals <45" apart. Spoke with CPO about installing plexiglass from bottom horizontal to top to eliminate horizontals and maintain 45" or greater. Permit denial.
Barrier with <45" between horizontals. Pool built in 1997. Barrier shall be at least 48" in height with 45" or greater between horizontals. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture <6 ft. from pool edge. Maintain 6 ft. clearance around the pool in all locations. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
300-29x chlorinator installed without flow meter. For NSF approval, install flow meter on inlet line to chlorinator. Original construction. If ever replaced, ensure repaired per NSF standard. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter was not operable. Corrected during the inspection.
Leak at the pump. Repair leak. Permit denial. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet due to leak at pump. Keep dry. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Labeling wearing off of pipes in pump room. Clearly identify all pipes with color codes or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >120 F. Maintain at 110 F or below. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in restrooms. Original construction. Provide hose bib with backflow prevention device. |