| Name | YMCA SIMMONS OUTDOOR | | Address | 6824 DEMOCRACY DR
| | | | City/State/ZIP | | | Premise Type | 50 - Seasonal Swimming Pool | | County | Mecklenburg | | Inspection Date
| 7/9/2021 | | Final Score @ Grade | | | Onsite visit to pool for in-field plan review. New pump installed. Pentair EQK 750, 7.5 hp pump. Electrical inspection passed.
Field verified -
1) Pentair EQK 750, 7.5 hp.
2) (1) 4" main drain and (2) 4" skimmer lines; (1) 4" return line.
3) (2) Paddock PCFC2424 drain covers
4) EQ lines plugged in skimmer/plastered on wall. One equalizer line plugged in incorrect hole. Operator was unable to plug during site visit. Provide documentation that correct line is plugged per State recommendations. Given until Monday July 12th to correct or permit will be suspended.
5) 28 floor returns
6) 13 skimmers
7) Verified chlorinator to detect flow.
8) No label on filter installed. Verified as Neptune Benson. Verified flow based on dimensions and spec sheet from mfg. Per contractor, Neptune Benson SHFFG 4860.
Pump approve. Ensure spare pump basket is provided.
Noted following items in need of correction prior to 2022 operating permit.
1) Flow meter not capable of reading 1.5xdesign flow of pump. Must read at least 525 gpm.
2) Zero entry - listed as 6". Must read 0 ft. 6 in. or 1/2 ft. on pool wall and deck in two locations. |
|