Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Observed main drains that were missing screws on all three covers. Must have approved screws on drains. Permit not issued. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(b) Two units of lifesaving equipment (or two lifeguards) must be provided for pools that exceed 3,000 sq. ft. surface area. PIC mentioned one lifeguard may be available and was missing second set of lifesaving equipment. CDI ring bouy provided and body hook on site. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. Observed latch that was less than 54” and missing coverings side of latch mechanism. Permit not issued.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door from restaurant leading to the pool that is not self latching or no alarm. Permit not issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft).
Observed chairs on side of pool causing less than 7ft clearance around pool.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
Observed holes in pool deck floors from a previous fence that was almost 1” and greater than 1/2” in size. Permit not issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Observed no backflow preventer on the hose bib. |