16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed Operator to not have access to clubhouse to confirm if doors to pool were self-closing/self-latching or if they were protected by an audible alarm. CDI: Operator gained access by end of inspection and it was found that the doors were not self-closing/self-latching and they did not have an alarm. Windows had inhibitors that came out from window frame that do limit window openings to less than 4 inches. Operator obtained two alarms for the two separate access doors by end of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed pump room floor with moisture under piping. Ensure pump room floor stays dry. .2533(d) Pump room floor shall be kept dry and free of standing water. Observed forced air fan not working. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |