Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed no updated paperwork for removal of equalizers. Facility is supposed to have 4 equalizers. All covers are missing, paperwork does nor reflect change. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed depth markers 30 FT apart. CDI- Marker placed between the 30Ft markers. |