8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Half of the skimmers not functioning. One of the skimmer valves turned off in the pump room. .2518(k) The flow-through rate through any one recessed automatic surface skimmer shall be between 20 gallons per minute and the maximum flow the skimmer is certified for under NSF Standard Number 50. Corrected by operator. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder loose. .2521 Install ladders per manufacturer instructions. |
|
13
|
4
|
Pool maintenance: contrasting band on steps and benches |
No |
No
|
No |
Contrasting color band as much as 1.5 inches from edge of the steps. .2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread. OR .2521(b) Provide at least 2" contrasting color band to edge of stair treads. This will need to be corrected before 2021 permit will be issued. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
New ring buoy and throw rope. .2530(a) Provide USCG approved ring buoy with 50 foot throw rope. Corrected by operator. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Pre-2010 gate with gap > 2" under the gate. .2528(a) Maintain 2" or less under the gate. This will need to be corrected before 2021 permit will be issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Vacuum cap missing. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Corrected by operator. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room light not functioning. .2533(b) Provide sufficient lighting in pump room. |