Premises Information

Return to Inspections
NameMAA SOUTH PARK
Address4835 CAMERON VALLEY PKWY
 
City/State/ZIP
CHARLOTTE NC 28210
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 5/20/2026
Final Score @ Grade
8
General CommentsEHS verified the following items onsite during inspection. 1. Pump 3 is a Pentair Intelliflo 3VSF 011076 3 Hp 2. For 2 pump system: 1 4inch main drain line, 2 3 inch skimmer lines, and 1 4 inch return line into the slab. 3. There is a total of 6 main drains in the pool. 4 Aquastar A10RCFRxxx 2017 drain covers. 4. Verified there is a Pentair sand filter onsite for pump 3. There is no data plate for sand filter. 5. 9 total skimmers 6. 26 total returns. NEW PERMIT RESTRICTION: All flow meters must remain operable. Flow Required on pump 3 (011076) at 93 GPM to 103 gpm so not to exceed return line from system (2”). Main flow meter at return line at slab shall be required at least 225 gpm to meet turnover. 93 gpm required to maintain minimum turnover combined with other 2 systems.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed minor debris in skimmer baskets.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed flow meter on return line reading 210 GPM, and flow meter for pump 3 reading 70 GPM during inspection. Pool tech was unable to turn up variable speed pump during inspection. Pool has the following permit restriction: All flow meters must remain operable. Flow required on pump 3 (011076) at 93gpm to 103gpm so not exceed return line from system (2”). Main flow meter at return line at slab shall be required at least 225 GPM to meet turnover. 93gpm required to maintain minimum turnover combined with other 2 systems. Permit Denied.