6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Observed pump on site (Pentair EQK 1500) does not match pump on submitted PDSC form (EQ 500). Permit denied.
Submit new PDSC form to reflect field conditions. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Surface skimmers shall be installed per manufacturer's instructions.
1 (E) (F) Be capable of providing continuous and automatic skimming of the water during quiescence;
Observed 2 skimmers on the lake side of the pool with no flow. |