Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed large breaks in the concrete where the concrete is degrading at the drain line and between the bricks and concrete. EHS has taken a video and will send to Katie Rudisill for consideration for next years inspection. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed wrong phone number stated on the information board. CDI-PO wrote the correct number on the board |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Observed a large leak coming out of the chlorine filter line. PO said chlorinator is currently not in use. CDI-PO fixed the line and is no longer leaking. |