Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Observed test kit reading 0ppm chlorine during inspection. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH of pool at 8.4 when tested. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed record keeping sheet that does not include daily checks of drain covers. Add section for checking drain covers to daily log sheet. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed missing weirs (flapping doors) in both of the skimmers. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Observed ladder missing rubber caps. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed large fitting missing near 3 FT depth marker (across from ladder), appears to be an overflow with a missing grate, safety hazard- large opening with potential to get hands/arm inside. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. Observed no body hook during inspection. Ensure body hook is attached to a NON collapsible pole. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Observed Kings III phone that was unable to connect to emergency operators. Message continued to repeat, no connection. Operators attempted to call Kings III during inspection, unable to fix during inspection. |