11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 - Rails and ladders shall be maintained in good repair. - Observed ladder on 5.5ft side of pool loose in need of tightening
down. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed throw rope to be 28FT. CDI- CPO- Provided rope at 29FT prior to the end of the inspection. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Observed dialing instructions faded and non legible on the emergency phone. CDI- CPO provided permanent dialing instruction on emergency phone prior to the end of the inspection. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(k) Provide shatterproof mirrors. - in the restrooms mirrors could not be verified to be shatterproof. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed hose bib near pool deck without backflow prevention device. |