Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Surface skimmers shall be installed per manufacturer's instructions. Observed all equalizer lines plugged on the inside of skimmers. CDI plugs removed. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. Observed one of the access gates swinging toward the pool and there was no barrier or egress to prevent it from swing away from the pool. Spoke with PEHS and they stated it was sufficient to issue permit but this item must be repaired prior to 2027 pool permitting. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Observed pool chairs creating less than 5ft walkway by side of the pool. Chairs moved.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed large cracks on the deck and in need of repair due to greater than 1/2” gap. CDI caulking started to repair issues |