6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form does not match what is installed. 1 1/2" pipe for skimmer return lines, not 2" as indicated on form by flow for equalizer line covers. Corrected PDSC form submitted and approved. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One of the throw ropes 52 feet. Corrected to 50 feet. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Some footholds on the outside of the fence. Maintain fence at least 48" high with no footholds. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Provide air gap for backwash. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water > 110F. Maintain at 110F or less. |