16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. Gate latch on inside of gate was able to be pushed by reaching hand through vertical bars. Gate has a combination lock on outside, however, management stated combination is automatically disabled during pool hours. Pool operator was able to secure sheet metal to gate during inspection to ensure area within 18 inches surrounding inside latch mechanism had no openings to be able to reach hand through. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2537(2) Decks shall be kept in good repair. Concrete deck has minor cracks near far side steps and ladder closest to gym. Repair deck. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Signage on premises had correct verbiage, however lettering was less than 4 inches. Management obtained correct signage during inspection.
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Signage on premises was incorrect. Management obtained correct signage during inspection.
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Signage on premises was incorrect. Management obtained correct signage during inspection. |