Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
2533(d) Pump room floor shall be kept dry and free of standing water. Observed outlet pipe from pump leaking at pipe joint. PO temporarily fixed with flex tape. Needs repair.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Hose bibs in restrooms and outside of clubhouse need backlow prevention devices. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Backwash is directly plumbed, no air gap.
GENERAL COMMENT: Permit issued. |