8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 1 loose weir and not properly installed. CDI: Weir properly installed. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed flow meter not functioning correctly. CDI: Carribbean pools arrived on site and corrected the issue.
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate. Observed flow meter maxes out at 60gpm. Provide flow meter that measures at least 75gpm. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed pipe for backwash is down in the drain. |