Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine at 0ppm. Permit denied |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 8.1. Permit denied |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Observed test kit with expired reagents. Permit denied |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed skimmer closest to pump room with equalizer line not plugged. PDSC form states all equalizers have been permanently disabled per state recommendations. Permit denied. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed vacuum line cover placed on return line. Provide return cover. Permit denied |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed torn ropes on ring buoy. Permit denied |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed small table directly beside pool water edge. Table was relocated. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2543(6) Automatic chemical controllers shall be provided to monitor and adjust disinfectant and pH for interactive play features. Observed chlorine pucks inside skimmers. CPO stated chlorinator is not operating properly. Permit denied. |