Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Observed top step on the ladder with screw missing causing the ladder’s step to only hold weight on one side. CDI- Screw was replaced during inspection by CPO. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed damaged ring buoy and rope. CDI- Both ring buoy and rope were placed during the inspection. Rope was cut to a length of 36 feet. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Distance from ground to bottom horizontal bar is as much as 8 inches in some areas and consistently greater than 4 inches around entire pool premiere. Pool built prior to 2010
Distance between horizontals on fence measured up to 5 1/2 inches. Pool built pre 2010. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
.2524(c) Lighting fixtures shall not present a hazard to the public. Observed light casing inside of the pool hanging with a protruding screw attached. Replaced during inspection by CPO to secure lighting fixture. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap. |