5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Maintain records of total alkalinity and cyanuric acid at least weekly. Observed TA and CA not being measured or recorded. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Observed main drain covers on pool floor not the same as the ones submitted on PDSC form. Submit proper information or change covers. IS issued. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed some discoloration/rough spots on pool floor and walls. Also observed several tiles broken along edge. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed one of two weirs missing. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed handrail at steps loose. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Provide properly working emergency phone. Observed dial tone however was unable to connect to 911 operator. Also clearly post address and phone number. Observed faded address and phone number at phone. IS issued. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Observed faded labels on pipes for backwash and return line in pump room. Corrected during inspection. |