Water quality: pool water pH |
No |
No
|
No |
Observed pH @ 7.1. **Maintain pH 7.2 to 7.8 (IS) |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Pool record missing documentation for 8 days thus far this month. No main drain checks. **CPO must inspect the pool daily & maintain written records of operating conditions - this includes daily main drain checks. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed scum on pool wall tiles. **clean.
Note: pool wall damaged from/ by ladder ends. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
At least 2 NO DIVING stickers peeling off pool deck. **correct. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from lobby into pool enclosure does not self-latch. **correct. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed deep chips out of pool deck in various areas. **correct. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed leak @ junction of pipe @ pump. **resolve so that equipment/ chemical room can stay dry. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash line is inserted down into slightly larger pipe. **backwash water should discharge through complete air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water ~126F at lavatories in lobby restrooms. **maximum allowed is 110F. |