Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. Two Aquastar covers missing at equalizer lines. Covers found in pump room storage. Covers reattached over equalizer lines. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Missing one weir. Replace. |
|
13
|
4
|
Pool maintenance: contrasting band on steps and benches |
No |
No
|
No |
.2521(b) Provide contrasting color band on leading edge of stair treads. Tile contrasting band has been painted over. Maintenance staff scraped paint off while on site. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed some areas of fencing with greater than 4 openings. Pool built prior to 2010 so no permit action.
.2528(a) Pool gate shall be at least 48" in height measured from outside of barrier. Observed gate at 45 inches in height. No permit action as pool was built prior to 2010. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Phone was hit by lightning and had to have new line run. Posted phone # did not match 911 number. Staff replaced posted number with new number given by 911 operator. REHS called number and phone rang back. |